Q1. For the circuit shown in Fig Q1, calculate EACH of the following:
(a) The current in each battery; (10)
(b) The load voltage; (3)
(c) The load power. (3)
Q2. When connected to a 20 V d.c. supply a relay starts to operate 0.52 ms after switching on the supply at which time the instantaneous current is 200 mA. The relay coil has a time constant of 5 ms.
(a) Calculate EACH of the following:
(i) The final steady state relay current; (6)
(ii) The resistance and inductance of the relay coil; (4)
(b) To increase the operating time a 40 Ω resistor is connected in series with the relay coil. Calculate the new operating time. (6)
Q3. A balanced, star connected, three phase load has a coil of inductance 0.2 H and resistance of 50 Ω in each phase. It is supplied at 415 V, 50 Hz. Calculate EACH of the following:
(a) The line current; (5)
(b) The power factor; (2)
(c) The value of each of the three identical delta connected capacitors to be connected to the same supply to raise the overall power factor to 0.9 lag; (7)
(d) The value of new line current. (2)
Q4. A three phase. 440 V, 60 Hz, 8 pole induction motor runs at a power factor of 0.85 lag and drives a load of 8 kW at a speed of 14.4 rev/s. The stator loss is 1 kW and the rotation losses (windage and friction) amount to 0.8 kW.
Calculate EAVH of the following:
(a) The synchronous speed; (3)
(b) The rotor copper loss; (5)
(c) The input power to the motor;(4)
(d) The motor current. (4)
Q5. A three phase, 440 V a.c. generator supplies the following loads:
i) 400 kW at a power factor 0.8 lagging
ii) 300 kW at unity power factor
iii) 250 kW at power factor 0.9 leading
Calculate EACH of the following:
(a) The total kW, kVA and kVAR supplied by the generator;(12)
(b) The generator current and power factor. (4)
Q6. A single phase, 50 Hz transformer has a turns ratio of 144 : 432 and a maximum flux of 7.5 mWb. The no load input is 0.24 kVA at 0.26 lagging. The transformer supplies a 1.2 kVA load at a power factor of 0.8 lagging.
(a) Magnetising current; (5)
(b) Primary current; (8)
(c) Primary power factor. (3)
Q7. With reference to an automatic voltage regulator (AVR) for ship’s a.c. generators:
(a) Explain why it is needed; (3)
(b) State two minimum performance criteria; (2)
(c) Sketch a clearly labelled block diagram; (6)
(d) Describe the operation of the block diagram sketched in Q7 (c). (5)
Q8. (a) Sketch a labelled diagram of power circuit for a star/delta starter. (8)
(b) Describe the sequence of operation of the circuit sketched in Q8(a)(6)
(c) State TWO limitations of the star / delta starting. (2)
Q9. An unstabilised d.c. supply voltage varies between 25 V and 35 V. A voltage stabiliser circuit comprising a 12 V zener diode and a series resistor R is connected across the unstabilised supply. The Zener has a slope resistance of 14 Ω and requires a minimum operating current of 1 mA. A 0-80mA variable load is to be supplied by the stabiliser circuit.
(a) When the supply voltage is minimum and the load current demand is a maximum, calculate EACH of the following:
(i) The maximum value for R to give a stable load voltage;(4)
(ii) The load voltage. (2)
(b) Using the value of R determined in Q9(a), calculate EACH of the following.
(i) The load voltage when the supply voltage and load current are both at maximum value. (4)
(ii) The Zener diode current when the supply voltage is minimum, and the load is switched off. (3)
(iii) The load voltage when the supply voltage is 30 V and the load current is 30 mA. (3)
Username or email address *Required
Password *Required
Note: Entering wrong username in the login form will ban your IP address immediately. Entering wrong password multiple times will also ban your IP address temporarily.
Log in
Lost your password? Remember me
No account yet?